ReviewBuilding
Review Date04/13/2016
StatusApproved
Comments
Sheet A009 Door & Storefront Systems Specifications & Schedules: Door EX01 is an existing entry door and indicates Hardware Set 8. Hardware does not include panic. Door 002 from the vestibule into the space has panic. Panic hardware is required in all A use spaces. VCC 2012 1008.1.10
Doors 7-10 for Toilet Rooms: Hardware Set 5 calls for passage set and deadbolt? Should these individual toilet rooms have privacy sets? Please clarify.
Door Type C: vision lites shall be 43" max aff ANSI A117.1 404.2.10
____________________________________________________________________
Hardware set for Doors 7-10 still not in compliance. Per VCC 1008.1.9.5, the unlatching of any door or leaf shall not require more than one operation. Deadbolts are not allowed. There cannot be a passage lever AND a deadbolt. A privacy lockset is required.
  



  
 